OCS 100 Occupancy Sensors |
|
OCS 100C |
Square feet coverage area | 2000 square feet |
| |
NOTE | These coverage dimensions are achieved when the OCS 100C is installed 10 ft (3.04 m) above the coverage area. |
|
|
OCS 100W |
Square feet coverage area | 1600 square feet |
| |
|
Sensor |
InteliDAPT® technology | Auto reset from test setting
Self-adjusting timer
Self-adjusting passive infrared thresholds
Automatic false-on and false-off correction |
LED lamp | Red - infrared motion
Green - ultrasonic detection |
Timer timeout | |
OCS 100C | Automatic mode: 8 to 42 minutes (self-adjusts based on occupancy)
Manual mode: 8 to 42 minutes
Test mode: 8 seconds |
OCS 100W | Automatic mode: 4 to 30 minutes (self-adjusts based on occupancy)
Manual mode: 4, 8, 15 and 30 minutes
Test mode: 8 seconds |
Ultrasonic (US) | |
OCS 100C | 4 sensors - 32 kHz output |
OCS 100W | 2 sensors - 32 kHz output |
Passive infrared (PIR) | |
OCS 100C | Dual-element pyrometer and 12-element cylindrical segmented Fresnel lens, integral filter excludes excess PIR energy from sunlight |
OCS 100W | Dual-element pyrometer and 12-element cylindrical rugged lens |
|
Relay |
Relay | 1 Normally Open and Closed contact, single pole, double throw 500 mA rated at 24 VDC, three-wire isolated relay |
|
Photocell |
Photocell | Adjustable natural-light override ranges from 1 to 100 foot-candles (10 to 1000 Lux) |
|
Adaptive functions |
Learning | 4 weeks for response error conditions, air current adaption and timer optimization |
Post-learning occupancy periods | 24-hour circadian occupancy periods learned |
Adjustments in post-learning period | Generally occupied periods
Generally unoccupied periods |
|
Digital output |
Quantity/type | 2 digital outputs |
Connectors | Blue wire = Occupancy only
Gray wire = Occupancy + Photocell |
Output voltage range | 0 - 24 VDC
Active high logic control signal with short-circuit protection, open collector when unoccupied |
|
General |
Sensor power input requirements | 20-24 VDC, 33 mA nominal |
NOTE | If power is supplied by an optional 12 VDC power supply, then use the included PC 1224 to convert 12 VDC to 24VDC. |
|
PC 1224 power requirements | Input: 12 VDC, 1.5 A max
Output: 12 VDC, 1.25 A max
24 VDC, 75 mA max |
Wiring | Color coded, pre-stripped leads - 6" (15 am) in total length |
Ambient temperature/humidity | Operation: +32 to +104 °F (0 to +40 °C) / 0% to 95 %, noncondensing
For indoor use only |
Cooling | Convection, no vents |
Mounting | Mounting base provided
Recommended mounting height: 8 feet with a max mounting height of 12 feet |
Enclosure type | Plastic |
Enclosure dimensions | |
OCS 100C | 4.50" W x 1.40" D
(114 mm W x 36 mm D) |
| |
OCS 100W | 2.80" W x 5.50" L x 2.10" D
(71 mm W x 140 mm x 53 mm D) |
| |
PC 1224 | 1.00" W x 1.00" L x 0.50" D
(25 mm W x 25 mm L x 13 mm D) |
Product weight | 0.1 lb (<0.1 kg) |
Color | Off-white |
Regulatory compliance | CE, c-UL, UL, FCC Class A, KC Complies with appropriate requirements of RoHS, WEEE, and California Title 24 |
Product warranty | 3 years parts and labor |
Everlast power supply warranty | 7 years parts and labor |
NOTE | Specifications are subject to change without notice. |
|
(5611-D6) |